ﻻ يوجد ملخص باللغة العربية
The resilience of Supervisory Control and Data Acquisition (SCADA) systems for electric power networks for certain cyber-attacks is considered. We analyze the vulnerability of the measurement system to false data attack on communicated measurements. The vulnerability analysis problem is shown to be NP-hard, meaning that unless $P = NP$ there is no polynomial time algorithm to analyze the vulnerability of the system. Nevertheless, we identify situations, such as the full measurement case, where it can be solved efficiently. In such cases, we show indeed that the problem can be cast as a generalization of the minimum cut problem involving costly nodes. We further show that it can be reformulated as a standard minimum cut problem (without costly nodes) on a modified graph of proportional size. An important consequence of this result is that our approach provides the first exact efficient algorithm for the vulnerability analysis problem under the full measurement assumption. Furthermore, our approach also provides an efficient heuristic algorithm for the general NP-hard problem. Our results are illustrated by numerical studies on benchmark systems including the IEEE 118-bus system.
The security of energy supply in a power grid critically depends on the ability to accurately estimate the state of the system. However, manipulated power flow measurements can potentially hide overloads and bypass the bad data detection scheme to in
The uncertainty of multiple power loads and re-newable energy generations in power systems increases the complexity of power flow analysis for decision-makers. The chance-constraint method can be applied to model the optimi-zation problems of power f
Given a network with the set of vulnerable actuators (and sensors), the security index of an actuator equals the minimum number of sensors and actuators that needs to be compromised so as to conduct a perfectly undetectable attack using the said actu
State estimation is a data processing algorithm for converting redundant meter measurements and other information into an estimate of the state of a power system. Relying heavily on meter measurements, state estimation has proven to be vulnerable to
We propose a framework for integrating optimal power flow (OPF) with state estimation (SE) in the loop for distribution networks. Our approach combines a primal-dual gradient-based OPF solver with a SE feedback loop based on a limited set of sensors