Design and Simulation of a Special Active Filter's Control System to Improve Electric Power Quality Using MATLAB


Abstract in English

This paper presents a three phase shunt Active Power Filter (APF) for power quality improvements in terms of harmonics compensation. The compensation process is based on measure non-liner load currents and Active Filter currents, and then extract the references from measured currents. Measured currents are then transferred from abc frame to d-q reference frame. A Synchronous Proportional Integral controller (Synchronous PI controller) is used. The control signals then drive the Pulse Width Modulation (PWM) routine, where its output controls the Voltage Source Inverter (VSI) switching devices. The performance of the Active Filter and the Synchronous PI controller is validated though the simulink results in MATLAB environment.

References used

Rudnick,H; Dixon,J; Morán,L. Delivering Clean and Pure Power. IEEE power & energy magazine, 2003
Kumar, P. Investigations on Shunt Active Power Filter For Power Quality Improvement. Thesis for the degree of Master of Technology, National Institute of Technology Rourkela University, Rourkela India,2007,67
Patidar, R; Singh, S. Active and Reactive Power Control and Quality Management in DG-GRID Interfaced Systems.ARPN Journal of Engineering and Applied Sciences,Vol.4,NO.3, May 2009,10