The output impedance matrix of a grid-connected converter plays an important role in analyzing system stability. Due to the dynamics of the DC-link control and the phase locked loop (PLL), the output impedance matrices of the converter and grid are difficult to be diagonally decoupled simultaneously, neither in the dq domain nor in the phase domain. It weakens the effectiveness of impedance-based stability criterion (ISC) in system oscillation analysis. To this end, this paper innovatively proposes the generalized-impedance based stability criterion (GISC) to reduce the dimension of the transfer function matrix and simplify system small-signal stability analysis. Firstly, the impedances of the converter and the grid in polar coordinates are formulated, and the concept of generalized-impedance of the converter and the grid is put forward. Secondly, through strict mathematical derivation, the equation that implies the dynamic interaction between the converter and the grid is then extracted from the characteristic equation of the grid-connected converter system. Using the proposed method, the small-signal instability of system can be interpreted as the resonance of the generalized-impedances of the converter and the grid. Besides, the GISC is equivalent to ISC when the dynamics of the outer-loop control and PLL are not considered. Finally, the effectiveness of the proposed method is further verified using the MATLAB based digital simulation and RT-LAB based hardware-in-the-loop (HIL) simulation.
The output impedance matrices of three-phase grid-connected voltage source converters (VSCs) are widely used in power system stability analysis. Regardless of how the impedance is modeled, there always exist coupling terms in the impedance matrix, wh
We apply a novel data-enabled predictive control (DeePC) algorithm in grid-connected power converters to perform safe and optimal control. Rather than a model, the DeePC algorithm solely needs input/output data measured from the unknown system to pre
The modern power system features high penetration of power converters due to the development of renewables, HVDC, etc. Currently, the controller design and parameter tuning of power converters heavily rely on rich engineering experience and extrapola
Stability of power grids with synchronous generators (SGs) and renewable generation interfaced with grid-forming converters (GFCs) under dc-side current limitation is studied. To that end, we first consider a simple 2-bus test system and reduced-orde
The grid-forming converter is an important unit in the future power system with more inverter-interfaced generators. However, improving its performance is still a key challenge. This paper proposes a generalized architecture of the grid-forming conve